Carbon Steel Press Fittings
Category:
Carbon steel press fittings
Summary:
Valve and pipe fittings: There are valves and pipe fittings, both of which are used in the connection or control system of pipelines, and none of them is indispensable.
UPC, CSA (LC 4),FM,UL, CRN
Key word:
Valve and pipe fittings
Description
Valve and pipe fittings: There are valves and pipe fittings, both of which are used in the connection or control system of pipelines, and none of them is indispensable.
Valves and fittings include carbon steel, stainless steel, cast steel, PVC, or other materials. The first three types of valves and fittings are commonly used. In recent years, with the improvement of people's living standards, the demand for non-staple food has also increased. This has led to the rapid development of food machinery, and the production of stainless steel sanitary grade valves and fittings has become popular. People often refer to valves and fittings as valve fittings, Most commonly used are stainless steel sanitary grade valve fittings
CARBON STEEL PRESS FITTINGS G
Designed for Gas & Fuel/Oil Piping System
Press carbon steel fittings with HNBR seal elements are suitable for natural gas, lubricating oil, fuel oil and
compressed air systems and are an alternative to welded, threaded and rolled-groove connections in new
installations and repairs and are not suitable for use in drinking water installations.
Application:
• Natural Gas (up to 125 PSI)
• Propane (up to 125 PSI)
• Mineral Oil (up to 200 PSI)
• Compressed Air (up to 200 PSI)
• Nitrogen (up to 200 PSI)
• Heating Fuel Oil (up to 125 PSI)
Certificates and Listings
• CSA: ANSI LC 4a/CSA 6.32a
• IAPMO: ANSI LC 4a/CSA 6.32a
Carbon Steel Press Fittings M
Designed For Mechanical and Fire Sprinkler Systems
Press carbon steel press accessories with EPDM sealing elements can be installed in NFPA 13, 13R and 13D
fire sprinkler systems. They are UL and FM certified for use in both "wet" and "dry" fire systems:
ANSI/CAN/UL 213: Standard for Rubber Gasketed Fittings for Fire- Protection Services.
FM Class 1920: Pipe Couplings and Fittings for Aboveground Fire- Protection Systems.
Application:
• Fire Sprinkler (up to 200 PSI)
• Chilled Water (up to 200 PSI)
• Hydronic Heating (up to 200 PSI)
• Low Pressure Steam (up to 15 PSI)
• Dry Compressed Air
• Technical Gases
Certificates and Listings
• UL 213 Listed
• ASTM F3226
• FM Class 1920
Previous page
None
Next page
Related products